Environmentally friendly gas-insulated metal-enclosed switchgear

The ESR-72.5kV series environmentally friendly gas-insulated metal-enclosed switchgear is rated for a voltage of 72.5kV and a frequency of 50Hz/60Hz. The main switch circuit is enclosed in a fully sealed tank-type gas chamber, which uses clean air as the insulating medium. The gas pressure is 0.5Mpa, and there are no fluorinated gases in the chamber, achieving green environmental protection.

Service Support:

  • Description
  •   Product Overview

      The ESR-72.5kV series environmentally friendly gas-insulated metal-enclosed switchgear is rated at 72.5kV with a rated frequency of 50Hz/60Hz. The main switch circuit is enclosed in a fully sealed tank gas chamber, which uses clean air as the insulating medium, with a gas pressure of 0.5Mpa, and contains no fluorinated gases, achieving green and environmentally friendly standards.

      The product adopts a three-phase common tube structure, with the circuit breaker arranged vertically, using vacuum interruption to achieve vacuum circuit breaker operation, ensuring long mechanical life and high reliability, with maintenance-free operation throughout its lifecycle. The isolating/grounding switch uses a three-position structure and can be configured with a fast grounding switch, featuring mechanical interlocking to eliminate misoperation and ensure high reliability. The operating mechanism is a spring-operated mechanism, safe and stable. The incoming and outgoing cables connect to the cabinet's main circuit through flood-proof cable plugs, ensuring safety and reliability throughout the entire operational lifespan.

      The product has good environmental adaptability and can be applied in humid, dirty, sandy, and cold environments, mainly suitable for use in offshore and onshore wind turbine towers and gathering stations.

      Environmental Conditions

      Altitude: ≤ 5000m (when the operating altitude exceeds 2000m, special instructions are required)

      Ambient Temperature: Maximum temperature +65℃, minimum temperature -50℃, average value within 24h ≤ 35℃

      Ambient Humidity: Average relative humidity within 24h ≤ 95%, average monthly relative humidity ≤ 90%.

      Pollution Level: Level 4

      Corrosion Level: Offshore C4H

      Seismic Level: AG5 (horizontal acceleration 0.3g, vertical acceleration 0.15g)

      Electromagnetic Interference: Induced electromagnetic interference amplitude in secondary systems ≤ 1.6kV

      Application Locations

      66kV voltage network inside offshore and onshore wind turbine towers, 66kV voltage network in offshore and onshore wind power gathering stations.

      66kV voltage network in offshore and onshore photovoltaic power generation outdoors and in box transformers, 66kV voltage network in offshore and onshore energy storage systems outdoors and in box transformers.

      Implementation Standards

      GB/T7674-2020 Gas-insulated metal-enclosed switchgear rated at 72.5kV and above; GB/T3906-2020 3.6kV~40.5kV AC metal-enclosed switchgear and control equipment.

      GB/T11022-2020 Common technical requirements for high-voltage AC switchgear and control equipment; GB/T1984-2014 High-voltage AC circuit breakers.

      GB/T16927.1~2-2013 High voltage test technology.

      GB/T3309-1989 Mechanical tests of high voltage switchgear at normal temperature; GB/T4473-2018 Synthesis tests of high voltage AC circuit breakers.

      GB/T5582-1993 External insulation pollution level of high voltage electrical equipment.

      GB/T11023-2018 Sealing test methods for high voltage switchgear using sulfur hexafluoride gas.

      DL/T593-2016 Common technical requirements for high voltage switchgear and control equipment.

      IEC62271-1:2017 Common technical requirements for high voltage switchgear and control equipment; IEC62271-100:2017 AC high voltage circuit breakers.

      IEC62271-200:2011 3.6kV~40.5kV AC metal-enclosed switchgear and control equipment; IEC62271-203:2011 Gas-insulated metal-enclosed switchgear rated at 52kV and above.

      IEC60694-2002 Common technical requirements for high voltage switchgear and control equipment; IEC60529 Enclosure protection level (IP code).

      Product Features

      Clean air insulation, achieving fluorine-free, green and environmentally friendly; vacuum circuit breaker operation, high number of operations, long electrical life; three-position switch, reliable interlocking.

      Isolation + fast grounding, high safety performance; modular design, strong versatility.

      Fully sealed design of the main switch circuit, protection level reaches IP67.

      Suitable for harsh environments such as humidity, achieving maintenance-free operation.

      Compact structure, small size, suitable for distribution inside wind turbine towers.

      Technical Parameters

    Name

    Unit

    Switchgear and Circuit Breaker Parameters

    Rated Voltage

    kV

    72.5

    Rated Frequency

    Hz

    50/60

    Rated Current

    A

    630   1250

    2500  3150

     

    Power Frequency Withstand Voltage

    Phase-to-phase, phase-to-ground, vacuum break.

     

    kV

    160

    Isolation Break.

    160+42

    Auxiliary and Control Circuits

    2

    Lightning Impulse Withstand Voltage

    Phase-to-phase, phase-to-ground, vacuum break.

    kV

    380

    Isolation Break.

    380+59

    Rated Short-Circuit Breaking Current

    kA

    31.5

    40

    Rated Short-Circuit Closing Current

    Circuit Breaker

    kA

    80

    100

    Grounding Switch

    80

    100

    Short-Time Withstand Current and Duration

    Main Circuit

     

    kA/s

    31.5/4

    40/4

    Grounding Switch

    31.5/4

    40/4

    Ground connection circuit

    27.4/2

    34.8/2

     

    Rated peak withstand current

    Main Circuit

     

    kA

    80

    100

    Grounding Switch

    80

    100

    Ground connection circuit

    69.6

    87

     

    Mechanical life

    Vacuum circuit breaker

     

    Times

    10000

    Isolating switch

    3000

    Grounding Switch

    3000

    Rated pressure

    Rated charging pressure (at 20℃
    Gauge pressure )

    MPa

    0.5

    Protection level

    Main switch circuit

     

    IP67

    Mechanism box

     

    IP55

    Vacuum circuit breaker level

     

    M2  E2  C2

    Insulating gas

     

    Clean air (environmental protection)/SF6 (optional)

    Annual relative gas leakage rate

    '%/ year'

    ≤ 0.01

    Circuit breaker rated operating sequence

     

    O-0.3s-CO-180s-CO(31.5kA) O-180s-CO-180s-CO(40kA)

    Expected service life

    Years

    40

    Operating voltage

    V

    AC/DC220

      Product dimensions

     

      Mainly used in offshore or onshore wind turbine towers for 66kV ring network system

      Mainly used in offshore or onshore 66kV collection system

Key words: